Cabinet-Mounted Dry Chemical Fire Suppression System

Cabinet-Mounted Dry Chemical Fire Suppression System

Poseidon supplies cabinet-mounted dry chemical fire suppression systems in PSSD30 and PSSD65 configurations. The PSSD30 has a listed agent charge of 30 kg and a 70 L storage container; the PSSD65 has a 65 kg charge and a 130 L container. Both offer automatic and manual activation for selected industrial fire hazards.

The systems use dry chemical agent for the specified Class A, B, and C hazards. Agent selection, quantity, piping, and nozzle arrangement must match the protected equipment or enclosure. Storage-container capacity alone does not define the protected floor area.

The listed discharge time is ≤30 seconds, with a storage pressure of 2.5 MPa at 20°C, a maximum working pressure of 3.1 MPa at 50°C, and an operating temperature range of −20°C to +50°C (−4°F to 122°F). Discharge duration is distinct from the time needed to extinguish a particular fire. Dry chemical leaves powder residue and requires post-discharge cleanup.

Compare these configurations within our dry chemical fire suppression system range. Specify the project hazard, layout, and required listing or approval documentation for the ordered system.

Cabinet-Mounted Dry Chemical Fire Suppression System Specifications

The PSSD30 and PSSD65 combine dry chemical storage with a cabinet-mounted arrangement for the selected installation. Both cabinets are listed at 550 mm long and 500 mm wide. The PSSD30 is 1740 mm high and the PSSD65 is 2240 mm high, with listed weights of 50 kg and 100 kg respectively. Allow installation and service access in addition to the cabinet footprint.

Automatic detection and manual activation must be coordinated with the releasing controls, distribution piping, nozzles, and the protected hazard. The listed electrical activation requirement is DC 24 V at ≤1.6 A. Choose the agent and discharge arrangement for the actual fuel and equipment rather than treating the system as universal protection for every industrial space.

For bulk or project supply, send the required model and quantity, fuel/fire hazards, enclosure or equipment dimensions, ventilation and openings, proposed cabinet and pipe locations, power and detection requirements, destination market, and required system approvals. Include installation drawings and labeling or packaging requirements where applicable so the system configuration and documentation can be specified together.

  • Two Agent-Charge Options: PSSD30 with 30 kg and PSSD65 with 65 kg, using 70 L and 130 L storage containers respectively.
  • Specified Fire Hazards: Select the dry chemical agent and system layout for the applicable Class A, B, or C hazards.
  • Automatic and Manual Activation: Coordinate detection and manual operation with the selected releasing and control arrangement.
  • Listed Discharge Time: ≤30 seconds for both configurations; this is a discharge specification rather than a universal extinguishment time.
  • Cabinet Installation: Compare the listed cabinet dimensions with the available location and maintenance access.
  • Inspection and Service: Plan inspections, agent servicing, and post-discharge restoration according to the system documentation.
  • Selected Machinery and Electrical-Equipment Hazards: Evaluate switchgear, transformer, and industrial equipment fire hazards using the specified agent and discharge design. Include powder cleanup and equipment restoration in the plan.
  • Flammable-Liquid Handling and Storage: Define the fuel, spill or equipment geometry, ventilation, and required protection arrangement for the selected hazard.
  • Industrial Production Areas: Match the system to the combustible materials, equipment layout, and enclosure or local protection requirements.
  • Garages and Logistics Facilities: Specify the actual equipment or storage hazard and system design; a cabinet model alone does not establish protection of an entire building.
Parameter PSSD30 PSSD65
Length 550 mm 550 mm
Width 500 mm 500 mm
Height 1740 mm 2240 mm
Weight 110 lbs (50 kg) 220 lbs (100 kg)
Dry Powder Storage Volume 70L 130L
Parameter PSSD30 PSSD65
Agent Charge 30 kg 65 kg
Discharge Time ≤ 30 seconds ≤ 30 seconds
Spray Residue Rate ≤ 10% ≤ 10%
Dry Powder Storage Container Volume 70L 130L
External Dimensions (mm) 550 x 500 x 1740±20 550 x 500 x 2240±20
Drawing Dimensions (mm) 530 x 500 x 1450 550 x 530 x 2000
Storage Pressure at 20°C 2.5 MPa 2.5 MPa
Activation Voltage/Current DC 24V ≤ 1.6A DC 24V ≤ 1.6A
Operating Temperature Range -20°C to +50°C -20°C to +50°C
Maximum Working Pressure at 50°C 3.1 MPa 3.1 MPa
  • System Listing and Approval: Specify the required UL listing or FM approval for the exact system model, components, and application. Supply documentation must match the ordered configuration.
  • NFPA 17: Design, installation, inspection, maintenance, and testing requirements for dry chemical extinguishing systems.
  • UL 1254: Safety and performance requirements for applicable fixed dry chemical system units; this differs from standards for portable extinguishers.
  • ISO 9001: Quality management system certification, rather than a fire-performance approval for an individual product.